System Voltage
Low Voltage Connections (up to 1000V)
The following standard voltages apply:
- Single phase connections; 230V (phase-neutral)
- Two and three phase connections; 230V (phase-neutral) and 400V (phase-phase)
- Split phase connections; 230V (phase-neutral) and 460V (phase-phase)
The voltage should remain within +10% and –6% of these figures.
High Voltage Connections (above 1000V)
Large commercial or industrial installations are often connected at high voltage. A number of different standard voltages are in use within Western Power Distribution’s area, including:
- 6600V (phase-phase)
- 11000V (phase-phase)
- 33000V (phase-phase)
- 66000V (phase-phase)
- 132000V (phase-phase)
The voltage should remain within ± 6% of the nominal connection voltage, with the exception of 132000V connections where the tolerance is ± 10%.